Welcome to MTU Online.
Please select your country and your language:

- Please select -
  • MTU-Global
  • Afghanistan
  • Åland
  • Albania
  • Algeria
  • American Samoa
  • Andorra
  • Angola
  • Anguilla
  • Antarctica
  • Antigua and Barbuda
  • Argentina
  • Armenia
  • Aruba
  • Australia
  • Austria
  • Azerbaijan
  • Bahrain
  • Bangladesh
  • Barbados
  • Belarus
  • Belgium
  • Belize
  • Benin
  • Bermuda
  • Bhutan
  • Bolivia
  • Bonaire, Sint Eustatius and Saba
  • Bosnia and Herzegovina
  • Botswana
  • Bouvet Island
  • Brazil
  • British Indian Ocean Territory
  • British Virgin Islands
  • Brunei
  • Bulgaria
  • Burkina Faso
  • Burundi
  • Cambodia
  • Cameroon
  • Canada
  • Cape Verde
  • Cayman Islands
  • Central African Republic
  • Chad
  • Chile
  • China
  • Christmas Island
  • Cocos (Keeling) Islands
  • Colombia
  • Comoros
  • Congo
  • Congo-Brazzaville
  • Cook Islands
  • Costa Rica
  • Côte d’Ivoire
  • Croatia
  • Cuba
  • Curaçao
  • Cyprus
  • Czech Republic
  • Denmark
  • Djibouti
  • Dominica
  • Dominican Republic
  • Ecuador
  • Egypt
  • El Salvador
  • Equatorial Guinea
  • Eritrea
  • Estonia
  • Ethiopia
  • Falkland Islands
  • Faroes
  • Fiji
  • Finland
  • France
  • French Guiana
  • French Polynesia
  • French Southern Territories
  • Gabon
  • Gambia
  • Georgia
  • Germany
  • Ghana
  • Gibraltar
  • Greece
  • Greenland
  • Grenada
  • Guadeloupe
  • Guam
  • Guatemala
  • Guernsey
  • Guinea
  • Guinea-Bissau
  • Guyana
  • Haiti
  • Heard Island and McDonald Islands
  • Honduras
  • Hong Kong SAR of China
  • Hungary
  • Iceland
  • India
  • Indonesia
  • Iran
  • Iraq
  • Ireland
  • Isle of Man
  • Israel
  • Italy
  • Jamaica
  • Japan
  • Jersey
  • Jordan
  • Kazakhstan
  • Kenya
  • Kiribati
  • Kuwait
  • Kyrgyzstan
  • Laos
  • Latvia
  • Lebanon
  • Lesotho
  • Liberia
  • Libya
  • Liechtenstein
  • Lithuania
  • Luxembourg
  • Macao SAR of China
  • Macedonia
  • Madagascar
  • Malawi
  • Malaysia
  • Maldives
  • Mali
  • Malta
  • Marshall Islands
  • Martinique
  • Mauritania
  • Mauritius
  • Mayotte
  • Mexico
  • Micronesia
  • Moldova
  • Monaco
  • Mongolia
  • Montenegro
  • Montserrat
  • Morocco
  • Mozambique
  • Myanmar
  • Namibia
  • Nauru
  • Nepal
  • Netherlands
  • Netherlands Antilles
  • New Caledonia
  • New Zealand
  • Nicaragua
  • Niger
  • Nigeria
  • Niue
  • Norfolk Island
  • North Korea
  • Northern Marianas
  • Norway
  • Oman
  • Pakistan
  • Palau
  • Palestine
  • Panama
  • Papua New Guinea
  • Paraguay
  • Peru
  • Philippines
  • Pitcairn Islands
  • Poland
  • Portugal
  • Puerto Rico
  • Qatar
  • Reunion
  • Romania
  • Russia
  • Rwanda
  • Saint Barthélemy
  • Saint Helena, Ascension and Tristan da Cunha
  • Saint Kitts and Nevis
  • Saint Lucia
  • Saint Martin
  • Saint Pierre and Miquelon
  • Saint Vincent and the Grenadines
  • Samoa
  • San Marino
  • São Tomé e Príncipe
  • Saudi Arabia
  • Senegal
  • Serbia
  • Serbia and Montenegro
  • Seychelles
  • Sierra Leone
  • Singapore
  • Sint Maarten
  • Slovakia
  • Slovenia
  • Solomon Islands
  • Somalia
  • South Africa
  • South Georgia and the South Sandwich Islands
  • South Korea
  • South Sudan
  • Spain
  • Sri Lanka
  • Sudan
  • Suriname
  • Svalbard
  • Swaziland
  • Sweden
  • Switzerland
  • Syria
  • Taiwan
  • Tajikistan
  • Tanzania
  • Thailand
  • The Bahamas
  • Timor-Leste
  • Togo
  • Tokelau
  • Tonga
  • Trinidad and Tobago
  • Tunisia
  • Turkey
  • Turkmenistan
  • Turks and Caicos Islands
  • Tuvalu
  • Uganda
  • Ukraine
  • United Arab Emirates
  • United Kingdom
  • United States
  • United States Minor Outlying Islands
  • Uruguay
  • US Virgin Islands
  • Uzbekistan
  • Vanuatu
  • Vatican City
  • Venezuela
  • Vietnam
  • Wallis and Futuna
  • Western Sahara
  • Yemen
  • Zambia
  • Zimbabwe
- Please select -
  • Brazilian Portuguese
  • Chinese (Simplified)
  • Dutch
  • English
  • French
  • German
  • Hindi
  • Indonesian
  • Italian
  • Japanese
  • Norwegian
  • Polish
  • Russian
  • Spanish
  • Thai
  • Turkish
  • Vietnamese
MTU

Diesel engines for Continuous / Prime / Peak applications - 50 Hz - 1500 rpm

Continuous (3A)

Continuous ratings apply to installations where one or several generator sets serve as utility. At constant or varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: power stations

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
12V 2000 G65 515 575 460 A2A Download
12V 2000 G65 515 575 460 W2A Download
16V 2000 G65 655 740 592 A2A Download
16V 2000 G65 655 740 592 W2A Download
12V 2000 B26F 665 750 600 A2A Download
16V 2000 B26F 709 800 640 A2A Download
18V 2000 G65 720 810 648 A2A Download
18V 2000 G65 720 810 648 W2A Download
18V 2000 B26F 887 1000 800 A2A Download
12V 4000 B24F 1310 1480 1184 W2A Download
16V 4000 G24F 1635 1875 1500 W2A Download
20V 4000 B24F 2000 2275 1820 W2A Download
20V 4000 B34F 2200 2500 2000 W2A Download

Prime (3B)

Prime ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: construction sites, remote areas

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
10V 1600 G10F 407 450 360 A2A Download
10V 1600 G20F 448 500 400 A2A Download
12V 1600 G10F 524 590 472 A2A Download
12V 1600 G20F 576 650 520 A2A Download
12V 2000 G25 580 650 520 A2A Download
12V 2000 G25 580 650 520 W2A Download
12V 2000 G16F 665 750 600 A2A Download
12V 2000 G65 695 780 600 A2A Download
12V 2000 G65 695 780 600 W2A Download
12V 2000 G26F 709 800 640 A2A Download
16V 2000 G16F 806 910 728 A2A Download
16V 2000 G25 810 910 728 A2A Download
16V 2000 G25 810 910 728 W2A Download
16V 2000 G65 890 1000 800 A2A Download
16V 2000 G65 890 1000 800 W2A Download
16V 2000 G26F 890 1000 800 A2A Download
16V 2000 G36F 1000 1135 908 A2A Download
18V 2000 G65 1000 1135 908 A2A Download
18V 2000 G65 1000 1135 908 W2A Download
18V 2000 G26F 1102 1250 1000 A2A Download
12V 4000 G14RF 1205 1365 1092 W2A Download
12V 4000 G14F 1420 1600 1280 W2A Download
12V 4000 G24F 1575 1800 1440 W2A Download
16V 4000 G14F 1798 2100 1680 W2A Download
16V 4000 G24F 1965 2250 1800 W2A Download
20V 4000 G14F 2200 2500 2000 W2A Download
20V 4000 G24F 2420 2800 2240 W2A Download
20V 4000 G34F 2590 3000 2400 W2A Download
20V 4000 G44F 2807 3250 2600 W2A Download

2)4000 G73 with 1200 rpm

Peak (3G)

Peak ratings apply to installations operating in support of utility networks or grids (especially when renewable power sources are used). At constant or varying load, the number of generator set operating hours is limited to 1000 hours per year. Full power output is available for 500 hours non-stop operation per year. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: peak shaving, grid stability and capacity programs

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
16V 2000 G26F 890 1000 800 A2A Download
18V 2000 G26F 1102 1250 1000 A2A Download
12V 4000 G14F 1420 1600 1280 W2A Download
12V 4000 G24F 1575 1800 1440 W2A Download
16V 4000 G14F 1798 2100 1680 W2A Download
16V 4000 G24F 1965 2250 1800 W2A Download
20V 4000 G14F 2200 2500 2000 W2A Download
20V 4000 G24F 2420 2800 2240 W2A Download
20V 4000 G34F 2590 3000 2400 W2A Download

Prime Power limited (3C)

Prime Power limited ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is limited to 1000 hours per year. A 10% overload capacity is available.
Main usage: peak shaving, grid stability

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
10V 1600 G40F 407 450 360 A2A Download
10V 1600 G50F 448 500 400 A2A Download
12V 1600 G40F 524 590 472 A2A Download
12V 1600 G50F 576 650 520 A2A Download

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.
    The kVA figures are calculated with a 0.8 power factor.
    Typical deductions for fan drive power and generator efficiency is applied for calculation
    and serves as guideline only.

Diesel engines for Continuous/Peak applications - 60 Hz - 1800 rpm

Continuous (3A)

Continuous Power ratings apply to installations where one or several generator sets serve as utility. At constant or varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: power stations

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
12V 4000 G73 (2) 870 988 790 W2A Download
16V 4000 G73 (2) 1140 1300 1040 W2A Download
12V 4000 B14S 1190 1375 1100 W2A Download
12V 4000 B24S 1420 1625 1300 W2A Download
16V 4000 B14S 1680 1875 1500 W2A Download
16V 4000 B24S 1950 2219 1775 W2A Download
20V 4000 B24S 2290 2625 2100 W2A Download
20V 4000 B44S 2490 2875 2300 W2A Download

2)4000 G73 with 1200 rpm

Prime (3B)

Prime Power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: construction sites, remote areas

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
10V 1600 G10S 465 519 415 A2A Download
10V 1600 G20S 511 563 450 A2A Download
12V 1600 G10S 561 625 500 A2A Download
12V 1600 G20S 608 688 550 A2A Download
12V 2000 G45 710 800 640 A2A Download
12V 2000 G45 710 800 640 W2A Download
12V 2000 G85 810 919 735 A2A Download
12V 2000 G85 810 919 735 W2A Download
16V 2000 G45 915 1038 830 A2A Download
16V 2000 G45 915 1038 830 W2A Download
16V 2000 G26S 998 1138 910 W2A Download
16V 2000 G85 1010 1156 925 A2A Download
16V 2000 G85 1010 1156 925 W2A Download
18V 2000 G85 1191 1375 1100 A2A Download
18V 2000 G85 1191 1375 1100 W2A Download
12V 4000 G73 (2) 1105 1250 1000 W2A Download
16V 4000 G73 (2) 1390 1575 1260 W2A Download
12V 4000 G14S 1520 1750 1400 W2A Download
12V 4000 G24S 1736 2000 1600 W2A Download
16V 4000 G14S 2020 2313 1850 W2A Download
16V 4000 G24S 2280 2625 2100 W2A Download
20V 4000 G14S 2490 2875 2300 W2A Download
20V 4000 G24S 2740 3188 2550 W2A Download
20V 4000 G44S 3010 3500 2800 W2A Download

2)4000 G73 with 1200 rpm

Peak (3G)

Peak Power ratings apply to installations operating in support of utility networks or grids (especially when renewable power sources are used). At constant or varying load, the number of generator set operating hours is limited to 1000 hours per year. Full power output is available for 500 hours non-stop operation per year. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: peak shaving, grid stability and capacity programs

Engine model kWm kVA1) kWe1) Cooling variant Spec Sheets
16V 2000 G26S 998 1138 910 W2A Download
12V 4000 G14S 1520 1750 1400 W2A Download
12V 4000 G24S 1736 2000 1600 W2A Download
16V 4000 G14S 2020 2313 1850 W2A Download
16V 4000 G24S 2280 2625 2100 W2A Download
20V 4000 G14S 2490 2875 2300 W2A Download
20V 4000 G24S 2740 3188 2550 W2A Download
20V 4000 G44S 3010 3500 2800 W2A Download

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.
    The kVA figures are calculated with a 0.8 power factor.
    Typical deductions for fan drive power and generator efficiency is applied for calculation
    and serves as guideline only.
2) 4000 G73 with 1200 rpm

Diesel engines for Continuous/Peak applications - switchable 50/60 Hz - 1500/1800 rpm

Continuous (3A)

Continuous ratings apply to installations where one or several generator sets serve as utility. At constant or varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: power stations

Engine model kWm
(50/60 Hz)
kVA1)
(50/60 Hz)
kWe1)
(50 / 60 Hz)
Cooling variant Spec Sheets
12V 4000 B24X (2) 1310 / 1420 1485 / 1625 1188 / 1300 W2A on request
16V 4000 B24X (2) 1635 / 1950 1865 / 2219 1492 / 1775 W2A on request

2) Available on request

Prime (3B)

Prime ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. Quoted ratings are in accordance with ISO 3046 and are capable of 10% overload.
Typical applications: construction sites, remote areas

Engine model kWm
(50/60 Hz)
kVA1)
(50/60 Hz)
kWe1)
(50 / 60 Hz)
Cooling variant Spec Sheets
10V 1600 B40S 448 / 511 500 / 563 400 / 450 A2A Download
12V 1600 B30S 524 / 561 590 / 625 472 / 500 A2A Download
12V 1600 B40S 576 / 608 650 / 688 520 / 550 A2A Download
12V 2000 B76 709 / 716 800 / 813 640 / 650 A2A Download
16V 2000 B76 890 / 998 1000 / 1138 800 / 910 A2A Download
18V 2000 B76 1102 / 1097 1250 / 1250 1000 / 1000 A2A Download
12V 4000 G14X (2) 1420 / 1520 1600 / 1750 1280 / 1400 W2A on request
12V 4000 G24X (2) 1575 / 1736 1800 / 2000 1440 / 1600 W2A on request
16V 4000 G14X (2) 1798 / 2020 2100 / 2313 1680 / 1850 W2A on request
16V 4000 G24X (2) 1965 / 2280 2250 / 2625 1800 / 2100 W2A on request

1) The quoted typical kVA / kWe ratings are based on typical generator efficiencies.
    The kVA figures are calculated with a 0.8 power factor.
    Typical deductions for fan drive power and generator efficiency is applied for calculation
    and serves as guideline only.
2) Available on request