Rating definition: Standby operation with variable load

Load factor: < 75%

Operating hours: Max. 1000 hours per year

Power: 10% overload capability (ICXN)

Series 956: operating hours max. 500h/year

Engine model   kW   rpm   Optimization
S60   272   1500   x
S60   272   1500   1
S60   291   1500   x
S60   321   1500   x
S60   321   1500   1
S60   362   1500   1
S60   411   1500   x
S60   411   1500   1
6R1600G40F   249   1500   x,1,8
6R1600G50F   274   1500   x,1,8
8V1600G40F   325   1500   x,1,8
8V1600G50F   358   1500   x,1,8
10V1600G40F   407   1500   x,1,8
10V1600G50F   448   1500   x,1,8
12V1600G40F   524   1500   x,1
12V1600G50F   576   1500   x,1
12V 4000 P63   1560   1500   x,1
16V 4000 P63   2080   1500   x,1
20V 4000 P63   2600   1500   x,1
12V956TB33   3750   1500   x
16V956TB33   5000   1500   x
20V956TB33   6250   1500   x
  • Intake air temperature: 25°C
  • Charge-air coolant temperature: 50°C
  • Site altitude above sea level: 100 m
  • Optimization:

       (x) Fuel consumption

       (1) TA-Luft (NOx <1500 mg/mN3) optimized

       (8) EU Nonroad directive 97/68 EC, Stage IIIA compliant