| Onsite Energy type | CHP type | Electrical Output | Thermal Output | Thermal Output | Energy input |
Methane number | |
|---|---|---|---|---|---|---|---|
| kWel | kWth | kW(°C) | total | ||||
| GC 119 N5 | ME 3066 D | 119 | 198 | - | 345 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 182 N5 | ME 3066 L | 182 | 279 | - | 520 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 201 N5 | ME 3066 L | 201 | 275 | 38 (40) | 576 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 232 N5 | ME 3042 D | 232 | 369 | - | 655 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 357 N5 | ME 3042 L | 357 | 529 | - | 987 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 385 N5 | ME 3042 ZH3 | 385 | 604 | 31 (40) | 1138 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 386 N5 | ME 3042 Z | 386 | 541 | 28 (40) | 1061 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 386 N5 | ME 3042 Z6 | 386 | 489 | 33 (40) | 999 | ≥70 | Modules for natural gas (90/70 °C) |
| GC 116 N5 | ME 3066 DH | 116 | 198 | - | 337 | ≥70 | Modules for natural gas (100/80 °C) |
| GC 165 N5 | ME 3066 LH | 165 | 256 | - | 479 | ≥70 | Modules for natural gas (100/80 °C) |
| GC 227 N5 | ME 3042 DH | 227 | 341 | - | 628 | ≥70 | Modules for natural gas (100/80 °C) |
| GC 323 N5 | ME 3042 LH | 323 | 485 | - | 907 | ≥70 | Modules for natural gas (100/80 °C) |
| GC 120 B5 | MB 3066 L7 | 120 | 160 | - | 334 | 45-65 % | Modules for bio/sewage gas (90/70 °C) |
| GC 150 B5 | MB 3066 L6 | 150 | 191 | - | 402 | 45-65 % | Modules for bio/sewage gas (90/70 °C) |
| GC 192 B5 | MB 3066 L4 | 192 | 214 | 29 (50) | 499 | 45-65 % | Modules for bio/sewage gas (90/70 °C) |
| GC 349 B5 | MB 3042 LH5 | 349 | 397 | 62 (50) | 947 | 45-65 % | Modules for bio/sewage gas (90/70 °C) |
| GC 350 B5 | MB 3042 L3 | 350 | 523 | - | 1002 | 45-65 % | Modules for bio/sewage gas (90/70 °C) |
| GC 370 B5 | MB 3042 L5 | 370 | 426 | 69 (50) | 955≥ | 45-65 % | Modules for bio/sewage gas (90/70 °C) |
| Onsite Energy type | Genset type | Electrical Output | Thermal Output | Thermal Output | Energy input |
Methane number | |
|---|---|---|---|---|---|---|---|
| kWel | kWth | kW(°C) | total | ||||
| GR 232 N5 | AE 3042 D | 232 | 213 | - | 655 | ≥70 | Generating sets for natural gas |
| GR 323 N5 | AE 3042 LH3 | 323 | 261 | - | 907 | ≥70 | Generating sets for natural gas |
| GR 357 N5 | AE 3042 L | 357 | 288 | - | 987 | ≥70 | Generating sets for natural gas |
| GR 386 N5 | AE 3042 L | 386 | 231 | 80 (40) | 1061 | ≥70 | Generating sets for natural gas |
| GR 120 B5 | AB 3066 L7 | 120 | 80 | - | 334 | 45-65 % | Generating sets for bio/sewage/landfill gas |
| GR 150 B5 | AB 3066 L6 | 150 | 119 | - | 402 | 45-65 % | Generating sets for bio/sewage/landfill gas |
| GR 192 B5 | AB 3066 L4 | 192 | 118 | 29 (50) | 499 | 45-65 % | Generating sets for bio/sewage/landfill gas |
| GR 349 B5 | AB 3042 LH5 | 349 | 204 | 62 (50) | 947 | 45-65 % | Generating sets for bio/sewage/landfill gas |
| GR 370 B5 | AB 3042 L5 | 370 | 241 | 69 (50) | 955 | 45-65 % | Generating sets for bio/sewage/landfill gas |
| Ambient temperature: | 25°C |
| Height above sea level: | 100 m |
| Ambient air pressure: | 1000 mbar |
| Relative humidity: | 30 % |
| Gas specification: | See MTU specifications |
| Emissions class: | 500 mg NOx/m3N (related to 5 % O2), other on request. |
| Onsite Energy type | Genset type | Electrical Output | Thermal Output | Thermal Output | Energy input |
Methane number | |
|---|---|---|---|---|---|---|---|
| kWel | kWth | kW(°C) | total | ||||
| GB 772 N5 | AoE 8V 4000 | 772 | 410 | 53 (40) | 1869 | ≥ 70 | Generating sets for natural gas without heat utilisation |
| GB 1166 N5 | AoE 12V 4000 | 1166 | 610 | 71 (40) | 2824 | ≥ 70 | Generating sets for natural gas without heat utilisation |
| GB 1562 N5 | AoE 16V 4000 | 1562 | 829 | 111 (40) | 3764 | ≥ 70 | Generating sets for natural gas without heat utilisation |
| GB 1948 N5 | AoE 20V 4000 | 1948 | 1021 | 134 (40) | 4717 | ≥ 70 | Generating sets for natural gas without heat utilisation |
| GR 772 N5 | AE 8V 4000 | 772 | 410 | 53 (40) | 1869 | ≥ 70 | Generating sets for natural gas incl. heat utilisation |
| GR 1166 N5 | AE 12V 4000 | 1166 | 610 | 71 (40) | 2821 | ≥ 70 | Generating sets for natural gas incl. heat utilisation |
| GR 1562 N5 | AE 16V 4000 | 1562 | 829 | 111 (40) | 3745 | ≥ 70 | Generating sets for natural gas incl. heat utilisation |
| GR 1948 N5 | AE 20V 4000 | 1948 | 1021 | 134 (40) | 4717 | ≥ 70 | Generating sets for natural gas incl. heat utilisation |
| GR 772 N5 | AoE 8V 4000 | 772 | 861 | 53 (40) | 1869 | ≥ 70 | Generating sets for natural gas incl. heat utilisation and exhaust gas heat |
| GR 1166 N5 | AoE 12V 4000 | 1166 | 1272 | 71 (40) | 2821 | ≥ 70 | Generating sets for natural gas incl. heat utilisation and exhaust gas heat |
| GR 1562 N5 | AoE 16V 4000 | 1562 | 1700 | 111 (40) | 3745 | ≥ 70 | Generating sets for natural gas incl. heat utilisation and exhaust gas heat |
| GR 1948 N5 | AoE 20V 4000 | 1948 | 2154 | 134 (40) | 4717 | ≥ 70 | Generating sets for natural gas incl. heat utilisation and exhaust gas heat |
| Ambient temperature: | 25°C |
| Height above sea level: | 400 m |
| Ambient air pressure: | 1000 mbar |
| Relative humidity: | 30 % |
| Gas specification: | See MTU specifications |
| Emissions class: | 500 mg NOx/m3N (related to 5 % O2), other on request. |
| Onsite Energy type | Gas turbine type | Power output | Emissions | |
|---|---|---|---|---|
| kW | ||||
| GB 22500 V5C | LM2500 | 22 500 | 13.BlmSchV | |
| GB 27000 V5C | LM2500 STIG | 27 000 | 13.BlmSchV | |
| GB 31200 V5C | LM2500+ | 31 200** | 13.BlmSchV |
* Central Europe only
** Various ratings available
STIG = Steam injection for power enhancement (max. 22.7 t/h)
| Natural gas fuel ISO-conditions: | |
| Ambient air pressure: | 1013 mbar |
| Ambient air temperature: | 15°C |
| Inlet/Exhaust pressure drop: | 0 mbar |
| Relative humidity: | 60 % |
Generator and gear losses considered.
Options:
- Fuels: Different natural gas, liquid fuel, dual fuel
- Water or stream injection for NOx-reduction
- DLE-Version (Dry-low-emissions combustion system) also available
Further technical data upon request.
| Onsite Energy type | Genset type | Power output | Emissions | Gas Type | |
|---|---|---|---|---|---|
| kWe | CO | ||||
| HM 300 N | HM300 | 250 | < 10 ppm | Natural gas | |
| HM 400 N | HM320 | 363 | < 30 ppm | Natural gas | |
| HM 300 B | HM300 | 250 | < 10 ppm | Bio gas | |
| HM 400 B | HM320 | 363 | < 30 ppm | Bio gas | |
| HM 300 S | HM300 | 250 | < 10 ppm | Sewage gas | |
| HM 400 S | HM320 | 363 | < 30 ppm | Sewage gas | |
| HM 300 M | HM300 | 250 | < 10 ppm | Methanol | |
| HM 400 M | HM320 | 363 | < 30 ppm | Methanol |
Description:
The fuel cell works at about 650 degrees Celcius and apart from power
also provides useful heat at a temperature of about 400 degrees Celcius.
This heat turns the Hotmodule into an interesting, decentralised small power station.